Skip to content
HeatSolve

Condensation

Nusselt's laminar-film analysis: vertical surfaces use h = 0.943·[g·ρ_l·h*_fg·k³/(μ·L·ΔT)]^1/4, a single horizontal tube uses the 0.729 constant with D, and N tubes in a vertical tier average down by N^-1/6. The modified latent heat h*_fg = h_fg(1 + 0.4·c_p·ΔT/h_fg) covers film subcooling.

Geometry

Film properties

Frequently asked

Why the modified latent heat?
The liquid in the film is cooler than saturation, so each kilogram condensed carries away more energy than h_fg alone. Nusselt's correction multiplies h_fg by (1 + 0.4·Ja); for small ΔT it is under 2 percent.
Why do stacked horizontal tubes condense slower?
The film from the upper tube floods the lower one, thickening the film below. The tier-average coefficient drops as N^-1/6 — a 10-tube tier runs at 68 percent of a single tube.
When does Nusselt's analysis break down?
It assumes a smooth, laminar film. Above roughly 30 K of ΔT the film becomes wavy and the real h is higher; the calculator warns when ΔT exceeds that band.